Flat vs Trefoil Formation
Script: examples/flat_vs_trefoil.py
Compares two common installation geometries for a symmetric 3-phase cable system: flat formation and trefoil formation.
Setup
Cable: 1 × 240 mm2 Cu XLPE, 20 kV (three identical single-core cables per formation)
Load: balanced 400 A per phase, constant for 48 hours
Soil: standard soil
Nominal depth: 1.0 m (centroid for trefoil)
- Flat formation
Three cables side-by-side, touching, at 1.0 m depth.
- Trefoil formation
Three cables in an equilateral triangle (touching), centroid at 1.0 m depth.
What it demonstrates
Setting up two different geometric configurations
Comparing peak conductor temperatures between formations
Assessing thermal asymmetry between phases (the centre cable in flat formation is hotter than the outer cables)
Custom matplotlib plots for direct phase-by-phase comparison
Output files
flat_vs_trefoil_cross_section.png— side-by-side cross-section comparisonflat_vs_trefoil_temperatures.png— conductor temperature traces for all six phases